Power Transformer Testing & Issue Detection With Omicron Equipment

Our client, a major utility provider in the UK, relied on a 33kV/11kV ONAN 25MVA power transformer as a critical asset within their transmission network. Given the age and strategic importance of this transformer, the client requested a comprehensive assessment of its health and performance, especially as the upcoming winter months demanded maximum reliability. Johnson & Phillips, with our expertise in transformer testing and diagnostics, was brought on board to conduct the tests.

The challenge

Project Scope

Our team was tasked with performing advanced diagnostic testing on the 25MVA transformer using the latest Omicron equipment, specifically the Testrano 600 and the Omicron FRAnalyzer (FRA) for Sweep Frequency Response Analysis (SFRA), to ensure a thorough evaluation of both electrical and mechanical integrity. The tests included:

  • Winding Resistance Measurement: To detect possible winding degradation and connection issues.
  • Dynamic Resistance Measurement: To evaluate tap changer condition under real-time load.
  • Sweep Frequency Response Analysis (SFRA): Using the Omicron FRAnalyzer to identify any potential winding displacement, core issues, or mechanical deformation.
  • Power Factor/Tan Delta Testing: To assess the insulation condition and detect moisture or contamination.
The solution

Testing Process

Upon initial inspection, our engineers conducted a series of baseline tests to assess the general health of the transformer. Utilizing the Testrano 600, we measured winding resistance and dynamic resistance values across all tap positions. This allowed us to analyze the stability of the tap changer and identify any resistive imbalances. The Omicron FRAnalyzer was then employed for detailed SFRA testing, providing critical insight into the state of the transformer’s core and winding structure.

Discovery of a Potential Asset-Destroying Issue

During the SFRA test, our engineers noticed a significant anomaly indicating possible core displacement. Further investigation with the FRAnalyzer revealed an unusual deviation in the frequency response, suggesting a loose core connection – a condition that, if left unchecked, could lead to excessive vibration, mechanical fatigue, and ultimately catastrophic failure of the transformer.

In addition, the dynamic resistance measurement revealed erratic readings on the tap changer, pointing to potential wear and tear that could cause severe operational issues under load. Our findings highlighted a probable asset-destroying issue, which could have led to costly unplanned outages for the client.

Recommendations

Based on our analysis, Johnson & Phillips recommended immediate remedial action to prevent further deterioration and extend the asset’s operational life:

  1. Core Re-Clamping: Engage in core tightening procedures to secure the connections and mitigate vibration issues.
  2. Tap Changer Overhaul: Schedule a maintenance overhaul to inspect and replace worn tap changer components.
  3. Enhanced Monitoring: Implement continuous online monitoring for early detection of future issues, reducing the likelihood of unexpected failures.
The result

Outcome

Our early detection enabled the client to proactively address critical issues before they could escalate, saving both repair costs and potential downtime. By partnering with Johnson & Phillips, the client gained valuable insights into the transformer’s health and a clear roadmap to bolster asset reliability.

This case exemplifies our commitment to leveraging cutting-edge testing equipment and diagnostic expertise to safeguard high-value assets in the power industry. With Johnson & Phillips, clients can trust that we deliver thorough and precise assessments, helping them maintain optimal performance and longevity of their vital infrastructure.

Contact Us

To learn more about how Johnson & Phillips can assist with your transformer testing needs, please reach out to us at:

  • Phone: 0121 328 9900
  • Email: service@johnsonphillips.co.uk

Lights out? We answer.

Network failure, tripped protection or a site that has gone dark. Our disaster recovery engineers are on call every hour of every day, arriving in minutes, not hours.

24/7 Emergency Line 01900 247 365