Click For Disaster Recovery 24/7 365 SupportCall 0800 86 000 86

Skip to main content
Johnson & PhillipsIntelligent Solutions for Power
Menu
  • Services
    • 11kV
    • 33kV
    • Transformer Testing
    • High Voltage Services
    • Distribution Transformers
    • Switchgear Systems
    • Diesel Generator Solutions UK
    • Circuit Protection
    • Power Factor Correction
    • Voltage Optimisation
    • Applied Power Services
  • Projects
  • About Us
  • Contact Us
  • Phone 0800 86 000 86
  • Phone
  • Email

Catastrophic Switchgear Failure

Healthcare

Our client is one of the largest hospital boards in Wales and serves the North. It has a major A&E unit as well as a vast amount of other departments.

The Challenge

During the January winter of 2016 one of the hospitals main switch rooms suffered a water leak. The results of this led to a huge flash-over in the main switchboard of this substation.
The switchboard was fed by two 1000kVA transformers running in parallel.

Due to the location of both incomers the failure melted the incoming section bus bars in this area. The section was isolated and sectioned via the bus coupler and the remainder of the switchboard was run via the hospitals standby generator.

The Solution

Johnson & Phillips  were called to site to provide their expert assessment of the damage along with another specialist company. Johnson & Phillips assessed the damaged switchboard section and our engineers advised they could repair it on site and in-situ.

The other company wanted to remove the end section and estimated eight weeks. Johnson & Phillips were chosen to carry out the works. Our engineers rebuilt the incoming section by renewing the damaged busbars and installed two new incoming air circuit breakers on-site and within three days of starting the works the incoming section was complete and re-energised.

The Results

Our engineers carried out the following:

  • Johnson & Phillips provided initial assessment.
  • Removed all the damaged bus bars.
  • Removed both incoming air circuit breakers.
  • Fabricated the new bus bars on-site.
  • Installed the new air circuit breakers.
  • Renewed all the control to align with the new ACB’s.
  • Tested and Commissioned.
  • Prev
  • Next
  • Safecontractor
  • Made in the UK
  • Delta

View Our RHA Conditions

© 2022 Johnson & Phillips (Capacitors) Limited. All rights reserved.
Johnson & Phillips (Capacitors) Limited, Agincourt Street Works, Newport, NP20 5JN.

All materials, including text and images, published on this website remain the copyright of Johnson & Phillips (Capacitors) Limited and are protected under copyright law & copy 2022. You may not, except with our express written permission, distribute or commercially exploit the content.

Modern Slavery Act | Policies | Social | News

  • Follow us:
  • Twitter
  • LinkedIn
  • Instagram